Thông số kỹ thuật Trip suppervision relay VDF-10 230VAC
F74 relay to suppervision trip-circuit of circuit breaker always in the ready state, it’s monitoring the power supply to circuit breaker tripping coil. It will alarm if voltage supply is low or power lost. Supervisory relays (F74) are widely used in relay protection panel.
- Number of contact: 2C/O
- Voltage control: 110Vdc; 230Vac; 220Vdc (Confirm voltage control when order)
- Product code: VDF-10 Vdc OP
- Socket flush mounting: F EMP TR OP
- Price included Relay + Socket
Monitoring is done by passing a small current through F74 relay connected with the tripping coil of breaker. The current flowing through this monitoring circuit is normally less than 1.4mA. Therefore, F74 relay have consumes power a very small.
Must be compatible with the tripping time of main protection relay. The tripping time of the circuit breaker must be less than 150ms, otherwise the relay will trip wrong and warning the trip-circuit is broken when main protection relay tripped.-
Lưu ý!
- Nhằm tránh trường hợp sản phẩm không đáp ứng được yêu cầu kỹ thuật, cũng như không lắp ráp được, khách hàng cần xem xét sản phẩm kỹ lưỡng và lựa chọn đúng nhà cung cấp.